    Requirements
  • 1.Rafters are to be overdrawn with a minimum 30 minute fire barrier (integrity and insulation) and this barrier should also be water resisting. 50 x 25mm battens are recommended on a micro-porous boarding to allow the thatch to breathe. (Dorset Fire and Rescue Service recommend a 60 minute barrier under the thatch for property protection).
  • 2. The chimney, including the pot, should terminate at least 1.8m above the height of the ridge. Due to the risk of condensation forming as hot gases cool, the chimney pots should be limited to a maximum height of 600mm.
  • 3. A domestic mains and battery powered, interlinked smoke alarm system will be required with one smoke alarm fitted in the roof void. The system should generally be in accordance with that specified in Approved Document B.
  • 4. The written comments of the adjoining property owner will be requested by the local authority for consideration.
  • 5. A terrace may not consist of more than three thatched dwellings together. In addition to the measures that may be required by Building Control there are a number of recommendations that you should carefully consider at an early stage.

    • Recommendations
  • 1. The provision of a loft hatch is recommended for fire fighting purposes. The minimum recommended size is 600mm x 900mm.
  • 2. Advice should be sought from an approved electrical contractor regarding the most appropriate types of wiring system. Effects from rodent damage and straw debris need to be considered.
  • 3. It is not recommended to cut in recessed lighting into the ceiling below the thatch. Light fittings within the roof space to be in a bulk head fitting. External floodlights should not be located just under thatch.
  • 4. Spark arrestors on the flues are not recommended because they can clog and restrict the flow of flue gases.
  • 5. It is recommended that an external water tap supplied from the rising main, is fitted with a hose capable of reaching all parts of the roof.
  • 6. Any metal plumbing in the roof space should use compression joints to avoid the use of blow torches.
  • 7. In order to achieve a ‘U’ value of 0.2w/m2K for thatched roofs, the following was taken from CIBSE Guide A3: Thatch: Reed = thermal conductivity 0.09, and ‘r’ 11.1
    Straw = thermal conductivity 0.07, and ‘r’ 14.3
    This gives a ‘U’ value of 0.2w/m2K for the following thickness
    Reed: 450mm
    Straw: 350mm
    The use of a flexible material as a fire resisting barrier is not considered acceptable for the purposes of the Dorset Model
    Tests carried out by The Thatch Register Limited
  • Fire Protection